Jon W

Jon W Job Checkin

Performed 8-12 tune-up and cleaning on 30+ year old boiler that was failing to maintain temperature above 60 degrees. Cleaned burners and burner chamber, but discovered severely plugged and deteriorating heat exchanger with dangerous CO readings (over 100 ppm in flue, 2 ppm leakage outside jacket). System operating at sub-70% efficiency with buzzing transformer/relays and leaking gate valve. Recommended immediate boiler replacement due to safety concerns.

Performed 8-12 tune-up and cleaning on 30+ year old boiler that was failing to maintain temperature above 60 degrees. Cleaned burners and burner chamber, but discovered severely plugged and deteriorating heat exchanger with dangerous CO readings (over 100 ppm in flue, 2 ppm leakage outside jacket). System operating at sub-70% efficiency with buzzing transformer/relays and leaking gate valve. Recommended immediate boiler replacement due to safety concerns. Performed 8-12 tune-up and cleaning on 30+ year old boiler that was failing to maintain temperature above 60 degrees. Cleaned burners and burner chamber, but discovered severely plugged and deteriorating heat exchanger with dangerous CO readings (over 100 ppm in flue, 2 ppm leakage outside jacket). System operating at sub-70% efficiency with buzzing transformer/relays and leaking gate valve. Recommended immediate boiler replacement due to safety concerns.

Jared R.

Jared R. Job Checkin

Responded to no-heat call for 5-year-old Lennox gas furnace (Model C35-24B-2F-2) which was not operating despite thermostat being set to heat. Diagnosed issue with hot surface ignitor not lighting. Inspected and cleared bugs from condensate lines and drain, then verified proper system operation through cycling test. System now functioning normally with proper ignition sequence and heating capability restored.

Responded to no-heat call for 5-year-old Lennox gas furnace (Model C35-24B-2F-2) which was not operating despite thermostat being set to heat. Diagnosed issue with hot surface ignitor not lighting. Inspected and cleared bugs from condensate lines and drain, then verified proper system operation through cycling test. System now functioning normally with proper ignition sequence and heating capability restored. Responded to no-heat call for 5-year-old Lennox gas furnace (Model C35-24B-2F-2) which was not operating despite thermostat being set to heat. Diagnosed issue with hot surface ignitor not lighting. Inspected and cleared bugs from condensate lines and drain, then verified proper system operation through cycling test. System now functioning normally with proper ignition sequence and heating capability restored.

Tony C.

Tony C. Job Checkin

Responded to service call for multiple plumbing issues. Inspected and replaced faulty cartridge in jacuzzi tub shower handle to resolve leakage issue. Also addressed hallway bathroom faucet repair as part of home inspection corrections for property sale.

Responded to service call for multiple plumbing issues. Inspected and replaced faulty cartridge in jacuzzi tub shower handle to resolve leakage issue. Also addressed hallway bathroom faucet repair as part of home inspection corrections for property sale. Responded to service call for multiple plumbing issues. Inspected and replaced faulty cartridge in jacuzzi tub shower handle to resolve leakage issue. Also addressed hallway bathroom faucet repair as part of home inspection corrections for property sale.

Tony C.

Tony C. Job Checkin

Responded to service call for toilet not flushing with reported empty tank. Upon inspection, toilet was functioning normally with proper fill and stop operation. Determined customer had misunderstood normal tank water level. Explained proper toilet operation to customer. No repairs needed as system was operating as designed.

Responded to service call for toilet not flushing with reported empty tank. Upon inspection, toilet was functioning normally with proper fill and stop operation. Determined customer had misunderstood normal tank water level. Explained proper toilet operation to customer. No repairs needed as system was operating as designed.

Scott N

Scott N Job Checkin

Responded to service call for restricted water flow to refrigerator. Diagnosed issue with existing fitting that was restricting water flow. Replaced defective fitting with appropriate connector to restore proper water supply to refrigerator.

Responded to service call for restricted water flow to refrigerator. Diagnosed issue with existing fitting that was restricting water flow. Replaced defective fitting with appropriate connector to restore proper water supply to refrigerator. Responded to service call for restricted water flow to refrigerator. Diagnosed issue with existing fitting that was restricting water flow. Replaced defective fitting with appropriate connector to restore proper water supply to refrigerator.

Roger M.

Roger M. Job Checkin

Performed scheduled furnace tune-up and identified a cracked heat exchanger, which was replaced to restore safe system operation. Inspected electrical connections at the breaker panel to ensure proper power supply to the unit.

Performed scheduled furnace tune-up and identified a cracked heat exchanger, which was replaced to restore safe system operation. Inspected electrical connections at the breaker panel to ensure proper power supply to the unit. Performed scheduled furnace tune-up and identified a cracked heat exchanger, which was replaced to restore safe system operation. Inspected electrical connections at the breaker panel to ensure proper power supply to the unit.

Roger M.

Roger M. Job Checkin

Responded to no-heat call. Upon arrival, system was operating normally with temperature at 69°F. Diagnostic testing revealed frost buildup on refrigerant lines, indicating possible refrigerant issues. Used digital measurement tools to verify system parameters. No repairs needed at time of service as unit was functioning properly.

Responded to no-heat call. Upon arrival, system was operating normally with temperature at 69°F. Diagnostic testing revealed frost buildup on refrigerant lines, indicating possible refrigerant issues. Used digital measurement tools to verify system parameters. No repairs needed at time of service as unit was functioning properly. Responded to no-heat call. Upon arrival, system was operating normally with temperature at 69°F. Diagnostic testing revealed frost buildup on refrigerant lines, indicating possible refrigerant issues. Used digital measurement tools to verify system parameters. No repairs needed at time of service as unit was functioning properly.

Roger M.

Roger M. Job Checkin

Responded to no-heat call for furnace less than 10 years old. Diagnosed system with dirty air filter restricting proper airflow. Replaced filter and advised customer to change monthly, more frequently during heavy usage periods. Unit now functioning normally with proper heat output.

Responded to no-heat call for furnace less than 10 years old. Diagnosed system with dirty air filter restricting proper airflow. Replaced filter and advised customer to change monthly, more frequently during heavy usage periods. Unit now functioning normally with proper heat output. Responded to no-heat call for furnace less than 10 years old. Diagnosed system with dirty air filter restricting proper airflow. Replaced filter and advised customer to change monthly, more frequently during heavy usage periods. Unit now functioning normally with proper heat output.

Tony C.

Tony C. Job Checkin

Responded to customer request regarding leaking garbage disposal. Upon inspection, confirmed active leak from existing unit. Removed failed disposal and installed new replacement garbage disposal, resolving the leak issue. System tested and functioning properly.

Responded to customer request regarding leaking garbage disposal. Upon inspection, confirmed active leak from existing unit. Removed failed disposal and installed new replacement garbage disposal, resolving the leak issue. System tested and functioning properly. Responded to customer request regarding leaking garbage disposal. Upon inspection, confirmed active leak from existing unit. Removed failed disposal and installed new replacement garbage disposal, resolving the leak issue. System tested and functioning properly.

Craig M.

Craig M. Job Checkin

Performed comprehensive maintenance on a 1-year-old furnace. Inspected heat exchanger for wear, conducted combustion analysis, verified proper gas pressure in high/low stages, and examined flame sensor, burners, and blower components. Services included cleaning flame sensor, flushing condensation trap, and clearing pressure switch. System is operating normally with no immediate concerns noted.

Performed comprehensive maintenance on a 1-year-old furnace. Inspected heat exchanger for wear, conducted combustion analysis, verified proper gas pressure in high/low stages, and examined flame sensor, burners, and blower components. Services included cleaning flame sensor, flushing condensation trap, and clearing pressure switch. System is operating normally with no immediate concerns noted. Performed comprehensive maintenance on a 1-year-old furnace. Inspected heat exchanger for wear, conducted combustion analysis, verified proper gas pressure in high/low stages, and examined flame sensor, burners, and blower components. Services included cleaning flame sensor, flushing condensation trap, and clearing pressure switch. System is operating normally with no immediate concerns noted.

Scott N

Scott N Job Checkin

Repaired water softener leak by properly repositioning clip on 12-4 hose. Identified main line drainage issue in house causing tub to drain slowly and referred customer to a specialized drain company for further assistance.

Repaired water softener leak by properly repositioning clip on 12-4 hose. Identified main line drainage issue in house causing tub to drain slowly and referred customer to a specialized drain company for further assistance. Repaired water softener leak by properly repositioning clip on 12-4 hose. Identified main line drainage issue in house causing tub to drain slowly and referred customer to a specialized drain company for further assistance.

Scott N

Scott N Job Checkin

Responded to service call for water line connection to Whirlpool refrigerator. Upon inspection, determined water supply system was functioning properly with adequate line pressure at the filter assembly, but no water was dispensing from the refrigerator outlet. Diagnosed issue as internal refrigerator malfunction rather than plumbing problem. Advised customer to contact Whirlpool manufacturer for warranty service.

Responded to service call for water line connection to Whirlpool refrigerator. Upon inspection, determined water supply system was functioning properly with adequate line pressure at the filter assembly, but no water was dispensing from the refrigerator outlet. Diagnosed issue as internal refrigerator malfunction rather than plumbing problem. Advised customer to contact Whirlpool manufacturer for warranty service. Responded to service call for water line connection to Whirlpool refrigerator. Upon inspection, determined water supply system was functioning properly with adequate line pressure at the filter assembly, but no water was dispensing from the refrigerator outlet. Diagnosed issue as internal refrigerator malfunction rather than plumbing problem. Advised customer to contact Whirlpool manufacturer for warranty service.

Jared R.

Jared R. Job Checkin

Conducted comprehensive natural gas line inspection throughout entire residence. Used gas detection equipment to verify integrity of all gas connections, fittings, and shut-off valves at appliances. Educated homeowner on proper emergency shut-off procedures and appliance relighting sequence.

Conducted comprehensive natural gas line inspection throughout entire residence. Used gas detection equipment to verify integrity of all gas connections, fittings, and shut-off valves at appliances. Educated homeowner on proper emergency shut-off procedures and appliance relighting sequence. Conducted comprehensive natural gas line inspection throughout entire residence. Used gas detection equipment to verify integrity of all gas connections, fittings, and shut-off valves at appliances. Educated homeowner on proper emergency shut-off procedures and appliance relighting sequence.

Chase O.

Chase O. Job Checkin

Successfully installed customer-supplied kitchen faucet with proper connection to existing plumbing. Completed installation of supply lines with color-coded hot and cold water connections and verified proper drainage system function. All connections were secured and tested for leaks prior to completion.

Successfully installed customer-supplied kitchen faucet with proper connection to existing plumbing. Completed installation of supply lines with color-coded hot and cold water connections and verified proper drainage system function. All connections were secured and tested for leaks prior to completion. Successfully installed customer-supplied kitchen faucet with proper connection to existing plumbing. Completed installation of supply lines with color-coded hot and cold water connections and verified proper drainage system function. All connections were secured and tested for leaks prior to completion.

Jon W

Jon W Job Checkin

Inspected client's gas valve system and confirmed all gas valves are properly positioned for safe operation. Verified complete functionality of the heating system with no safety concerns identified. Instructed homeowner on proper system handling to maintain optimal operation and safety.

Inspected client's gas valve system and confirmed all gas valves are properly positioned for safe operation. Verified complete functionality of the heating system with no safety concerns identified. Instructed homeowner on proper system handling to maintain optimal operation and safety.